General |
Topology |
Online (Double Conversion) |
Configuration |
Rackmount |
Part Number |
PW9130G2000R-XL2UAU |
Color |
Black |
Rating (VA/Watts) |
2000/1800 |
Diagnostics |
Full system self-test |
Efficiency |
94% in high-efficiency mode; 90% in online mode |
UPS Bypass |
Automatic bypass |
Dimensions (H x W x D, mm) |
86.5 x 438 x 600 |
Weight (kg) |
29 |
Rail Kit Included |
Yes |
Remote Emergency Power off (REPO) |
Emergency shutdown control through the REPO port |
|
Electrical Input |
Connection |
(1) IEC-320-C14
|
Input Cord |
Aust. 10A to IEC 320-10A |
Input Voltage Range |
180-276 Vac (with load PF of 0.7) |
Nominal Voltage |
220-240 V |
Frequency |
50/60 Hz |
Frequency Range |
4565 Hz |
Nominal Current |
8.7A @230V |
Breaker Ratings |
10A |
|
Electrical Output |
Output Receptacles |
(4) IEC-320-C13
(4) Aust. 10A
|
On Utility Voltage Regulation |
3% of nominal |
On Battery Voltage Regulation |
3% of nominal |
Frequency Regulation |
3% Hz online |
Load Crest Factor |
3 to 1 |
|
Battery |
Runtime (minutes)
Load (watts)
200
400
600
800
1000
1200
1400
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
|
Standard runtime |
|
with 1 ebm |
|
with 2 ebms |
|
with 3 ebms |
|
with 4 ebms |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
Battery Description |
VRLA 12V/9 Ah (internal and External) |
Battery Type |
Replaceable maintenance free sealed lead acid |
Battery Replacement |
Hot-swappable internal batteries |
Start On Battery |
Allows start of UPS without utility input |
|
Communications |
User Interface |
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
LEDs |
Four status-indicating LEDs |
Communication Ports |
RS-232 and USB HID port as standard |
Relay Output |
Common alarm standard |
Communications Slot |
Optional communication slots (BD Slot) |
Communications Card Slots |
Optional SNMP/Web card for monitoring in SNMP-based networks, monitoring through Web browser interface. Relay card for integration to industrial environment and BMS, remote shutdown for IBM AS/400 systems |
|
Environmental & Standards |
Heat Dissipation (BTU) |
Line: 838, Bat: 1348 |
Audible Noise |
<44 dB |
Operating Temperature |
0C to +40C |
Performance - Safety - EMC |
CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2), GS |
Storage Temperature |
-20C to +40C with batteries and -25C to +55C without batteries |
Relative Humidity |
590% non-condensing |