All stock codes associated to this product
SUVTP10KH3B4S, 1034506, 731304202851, 7330381070709
SUVTP10KH3B4S
APC Smart-UPS VT 10kVA 400V w/3 Batt Mod Exp to 4, Start-Up 5X8, Int Maint Bypass, Parallel Capable
APCSmart-UPS VT, 8000 Watts / 10 kVA,Input400V 3PH / Output400V 3PH, Interface Port DB-9 RS-232, Smart-Slot, Extended runtime model
Includes: Battery modules ship installed, Bolt down brackets, CD with software, Installation guide, Network Management Card, Power modules ship installed, Start up included, User Manual
Parallel-capacity capable
Increases total power capacity by using multiple UPSs simultaneously.
Parallel-redundant capable
Power the connected equipment with multiple UPSs to increase system redundancy
Smart-UPS VT Features & Benefits
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Scalable runtime
Allows additional run time to be quickly added as needed.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS overload condition or fault.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Battery replacement without tools
Allows quick, easy battery replacement.
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Shippable with modules installed
Enables pre-installation UPS staging and testing and faster installation.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Network manageable
Provides remote management of the UPS over the network.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Audible alarms
Provides notification of changing utility power and UPS conditions.
Programmable frequency
Ensures compatibility with different input frequencies.
LED status indicators
Quickly understand unit and power status with visual indicators.
SmartSlot
Customize UPS capabilities with management cards.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Cold-start capable
Provides temporary battery power when the utility power is out.
Specifications
Output Power Capacity
8000Watts /10 kVA
Max Configurable Power
8000Watts /10 kVA
Nominal Output Voltage
400V 3PH
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load
95%
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal
Output Connections
(1) Hard Wire 4-wire (3PH + G) |
|
(1) Hard Wire 5-wire (3PH + N + G) |
|
(1) Screw Terminals |
|
Bypass
Built-in Maintenance Bypass,Built-in Static Bypass
Nominal Input Voltage
400V 3PH
Input Frequency
40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 5-wire (3PH + N + G) |
|
Input voltage range for main operations
304 - 477V
Other Input Voltages
380,415
Maximum Input Current
14A
Input Breaker Capacity
20A
Included Battery Modules
3
Available Battery Slots
1
Typical recharge time
5hour(s)
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage
+/-154 V
Extended Run Options
APC Smart-UPS VT 10kVA 400V w/3 Batt Mod Exp to 4, Start-Up 5X8, Int Maint Bypass, Parallel Capable
Communications & Management
Interface Port(s)
DB-9 RS-232,Smart-Slot
Pre-Installed SmartSlot Cards
AP9631
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Shipping Height
1643.00mm
Operating Environment
0 - 40C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-999.9meters
Storage Temperature
-50 - 40C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000meters
Audible noise at 1 meter from surface of unit
64.00dBA
Online Thermal Dissipation
1774.00BTU/hr
Regulatory Approvals
C-tick,CE,EN 50091-2,EN/IEC 62040-3,IEC 61000-3-2,IEC 61000-3-3,ISO 14001,ISO 9001,VFI-SS-112
Standard Warranty
1 year repair or replace,Start-Up Service