General |
Topology |
On-line double conversion with automatic by-pass and power factor correction |
Configuration |
Rack/Tower |
Part Number |
M68184 |
Color |
metallic grey |
Rating (VA/Watts) |
1500/1350 Maximum rating with EXB battery units: 1200 W |
Dimensions (H x W x D, mm) |
86.5 x 438 x 483 |
Weight (kg) |
20.5 |
Warranty |
2 years warranty, Standard product exchange, including the battery |
Rail Kit Included |
Yes |
|
Electrical Input |
Connection |
(1) IEC-320-C14
|
Input Voltage Without Using Batteries |
100/120/140/160 V to 284V Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively |
Input frequency Range Without Using Batteries |
40 to 70 Hz |
|
Electrical Output |
Voltages |
230 V (adjustable to 200/208/220/240/250 V), |
Output Receptacles |
(6) IEC-320-C13
|
Remotely controlled sockets |
2 independent groups: 2 + 1 IEC C13 (10A) sockets |
Output Frequency |
50/60 Hz auto-select or frequency converter mode (derated by 15% when used as a frequency converter) |
|
Battery |
Runtime (minutes)
Load (watts)
200
400
600
800
1000
1200
0
100
200
300
400
500
600
700
|
Standard runtime |
|
with 1 ebm |
|
with 2 ebms |
|
with 3 ebms |
|
with 4 ebms |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
Battery Management |
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units =>continuous maximisation of backup time + deep discharge protection |
|
Communications |
User Interface |
(3) LEDs + adjustable multilingual display: display of measurements, access to control and setup menus |
Communication Ports |
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 serial ports cannot be used simultaneously) 1 mini terminal block for remote ON/OFF and emergency stop |
Communications Card Slots |
1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial |
|
Environmental & Standards |
Audible Noise |
45 dBA |
Operating Temperature |
0C to 40C continuous |
Performance - Safety - EMC |
IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class |
Approvals |
CE, TV GS, CB report, cTV-US |