Electrical Input |
Connection |
Hardwired - see manual for terminal block layout
|
Input Voltage Range |
176-276V without derating (up to 100276V with derating) |
Nominal Voltage |
200/208/220/230/240V |
Frequency |
50/60 Hz autoselection |
Frequency Range |
40-70 Hz |
Short Circuit Current |
90 A |
THDI |
<5% |
|
Electrical Output |
Voltages |
200/208/220/230/240V +/ 1% |
Voltage THD |
< 2% |
Output Receptacles |
(8) IEC-320-C13
(2) IEC-320-C19
Hardwired - see manual for terminal block layout
|
Overload Capacity |
102110% : 120s, 110125%: 60s, 125150%: 10s, >150%: 500ms |
Efficiency (Normal Mode) |
Up to 94% in Online mode, 98% in Hi-Efficiency mode |
Output Frequency |
50/60 Hz autoselect, frequency converter as standard |
Load Crest Factor |
3:1 |
|
Battery |
Runtime (minutes)
Load (watts)
500
1000
1500
2000
2500
3000
3500
4000
4500
0
100
200
300
400
500
600
700
800
900
1000
|
Standard runtime |
|
with 1 ebm |
|
with 2 ebms |
|
with 3 ebms |
|
with 4 ebms |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
Battery Management |
ABM and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Extended Battery Capability |
EBM with Rack Kit |
|
Communications |
User Interface |
Multilingual graphical LCD display |
Communication Ports |
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off |
Communications Slot |
1 slot for Network-MS card, ModBus-MS or Relay-MS cards. |
|
Environmental & Standards |
Audible Noise |
<45dB |
Operating Temperature |
0 to 40C continuous |
Safety markings |
IEC/EN 62040-1, UL 1778, CSA 22.2 |
EMC Markings |
IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance), C-Tick |
Approvals |
CE, CB report (TUV), UL |