SURTD3000XLIM
APCMarine,2100 Watts /3000 VA,Input230V /Output230V, Interface Port RJ-45 Serial, Smart-Slot, Extended runtime model, Rack Height 3U
Includes: CD with software, Smart UPS signalling RS-232 cable, User Manual
Product Overview
Marine Features & Benefits
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Pure sine wave output on battery
Simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
LED Indicators
Provide easy-to-read status of the unit and utility power conditions.
Serial connectivity
Provides management of the UPS via a serial port.
SmartSlot
Customize UPS capabilities with management cards.
Easy to install
Innovative design allows for fast, easy installation by almost anybody.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Technical support
Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Technical Specifications
Output Power Capacity
2100Watts /3000 VA
Max Configurable Power
2100Watts /3000 VA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Output Voltage Distortion
Less than 3%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Other Output Voltages
220, 240
Topology
Double Conversion Online
Output Connections
(8) IEC 320 C13 |
|
(2) IEC 320 C19 |
|
(2) IEC Jumpers |
|
Bypass
Internal Bypass (Automatic and Manual)
Nominal Input Voltage
230V
Input Frequency
50/60 Hz +/- 5 Hz (auto sensing)
Input Connections
British BS1363A |
|
IEC-320 C20 |
|
Schuko CEE 7/EU1-16P |
|
Input voltage range for main operations
180 - 270V
Input voltage adjustable range for mains operation
100 - 280V
Other Input Voltages
220, 240
Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules
2
Typical recharge time
2.50hour(s)
Replacement Battery
RBC44
Extended Run Options
APC Smart-UPS RT 3000VA 230V - Marine
Curve |
Part Number(s) |
A |
SURTD3000XLIM |
B |
SURTD3000XLIM + (1)SURT192XLBP |
C |
SURTD3000XLIM + (2)SURT192XLBP |
D |
SURTD3000XLIM + (3)SURT192XLBP |
E |
SURTD3000XLIM + (4)SURT192XLBP |
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Load |
Efficiency |
25% |
87.6% |
50% |
91.2% |
75% |
92.0% |
100% |
92.0% |
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output.
Communications & Management
Interface Port(s)
RJ-45 Serial, Smart-Slot
Available SmartSlot Interface Quantity
1
Control panel
LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators
Audible Alarm
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Surge energy rating
555JJoules
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Operating Environment
0 - 55C
Operating Relative Humidity
0 - 95% no%
Operating Elevation
0-3000meters
Storage Temperature
-15 - 45C
Storage Relative Humidity
0 - 95% no%
Storage Elevation
0-15000meters
Audible noise at 1 meter from surface of unit
55.00dBA
Online Thermal Dissipation
609.00BTU/hr
Regulatory Approvals
CE, DNV, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, KCC
Standard Warranty
2 years repair or replace, optional extended warranties available, optional on-site services available
REACH
REACH: Contains No SVHCs
PEP
Available in Documentation tab