All stock codes associated to this product
SRT6KXLI, 2690207, 731304301660
Smart-UPS On-Line
APC Smart-UPS SRT 6000VA 230V
SRT6KXLI
APCSmart-UPS On-Line,6000 Watts /6000 VA,Input230V /Output230V, Interface Port Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB, Extended runtime model
Includes: CD with software, Documentation CD, Installation guide, Removable support feet, Temperature Probe, USB cable, Warranty card
Product Overview
SRT6KXLI Features
LCD graphics display
Text and mimic diagrams that display modes of operation, system parameters and alarms.
10/100 BaseT Connection
Connect the device to a network using a 10 or 100 BaseT connection
Green mode
Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
Battery failure notification
Provides early-warning fault analysis on batteries enabling timely preventive maintenance
Smart-UPS On-Line Features & Benefits
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Scalable runtime
Allows additional run time to be quickly added as needed.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Network manageable
Provides remote power management of the UPS over the network.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
SmartSlot
Customize UPS capabilities with management cards.
LED status indicators
Quickly understand unit and power status with visual indicators.
Serial connectivity
Provides management of the UPS via a serial port.
Plug-and-Play external batteries
Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Rack/Tower convertible
Protects the initial investment in the UPS when migrating from tower to rack-mount environment.
Flash upgradeable firmware
Install maintenance releases of firmware remotely using FTP.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Predicitive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
Disconnected battery notification
Warns when a battery is not available to provide backup power.
Audible alarms
Provides notification of changing utility power and UPS power conditions
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Cold-start capable
Provides temporary battery power when the utility power is out.
Resettable circuit breaker
Easy recovery from overloads; no need to replace a fuse.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Specifications:
Output Power Capacity
6000Watts /6000 VA
Max Configurable Power
6000Watts /6000 VA
Nominal Output Voltage
230V
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Other Output Voltages
220, 240
Topology
Double Conversion Online
Output Connections
(1) Hard Wire 3-wire (H N + G) |
|
(6) IEC 320 C13 |
|
(4) IEC 320 C19 |
|
(2) IEC Jumpers |
|
Bypass
Internal Bypass (Automatic and Manual)
Nominal Input Voltage
230V
Input Frequency
45 - 65 Hz (auto sensing)
Input Connections
Hard Wire 3 wire (1PH+N+G) |
|
Input voltage range for main operations
160 - 275V
Input voltage adjustable range for mains operation
100 - 275V
Other Input Voltages
220, 240
Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
1.50hour(s)
Replacement Battery
APCRBC140, SRT10KXLT, SRT10KXLT-IEC, SRT10KRMXLT, SRT10KRMXLT-IEC, SRT5KXLT, SRT5KXLT-IEC, SRT5KRMXLW-HW, SRT5KRMXLT, SRT5KRMXLT-IEC, SRT6KXLT, SRT6KXLT-IEC, SRT6KRMXLT, SRT6KRMXLT-IEC, SRT8KXLT, SRT8KXLT-IEC, SRT8KRMXLT, SRT8KRMXLT-IEC
Extended Run Options
APC Smart-UPS SRT 6000VA 230V
Curve |
Part Number(s) |
A |
SRT6KXLI |
B |
SRT6KXLI + (1)SRT192BP |
C |
SRT6KXLI + (2)SRT192BP |
D |
SRT6KXLI + (3)SRT192BP |
E |
SRT6KXLI + (4)SRT192BP |
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Load |
Efficiency |
25% |
92.7% |
50% |
94.4% |
75% |
94.6% |
100% |
94.4% |
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit of data measured in accordance with the ENERGY STAR Program Requirements Product Specification for Uninterruptible Power Supplies (UPSs) - Eligibility Criteria Version 1.0. All measurements taken in normal mode(s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output.
Communications & Management
Interface Port(s)
Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB
Available SmartSlot Interface Quantity
1
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Surge energy rating
480Joules
Operating Environment
0 - 40C
Operating Relative Humidity
0 - 95% no%
Operating Elevation
0-3000meters
Storage Temperature
-15 - 45C
Storage Relative Humidity
0 - 95% no%
Storage Elevation
0-15000meters
Audible noise at 1 meter from surface of unit
55.00dBA
Online Thermal Dissipation
1300.00BTU/hr
Regulatory Approvals
CE, CE Mark
Standard Warranty
3 years repair or replace (excluding battery) and 2 years for battery
REACH
REACH: Contains No SVHCs