General
|
Dimensions (H x W x D, mm) |
90 x 70 x 58 |
Weight (g) |
200 |
Warranty |
5 years, workmanship and materials |
Installation instructions |
Supplied with unit |
Number of ports |
1 Port |
Method of mounting |
Fixed. DIN Rail mount |
|
|
Electrical |
Input voltage |
380-480vac 3P
|
Maximum continuous operating voltage (MCOV) |
320 L-N |
Temporary overvoltage - TOV |
350VAC L-N, 15 mins |
Service Type |
TT, TN, TN C-S 3 phase system with a grounded neutral. |
Test classification (IEC61643-11) |
Class II |
Protection modes |
Line-Earth, Neutral-Earth |
Inom 8/20us (Line-Neutral). Nominal surge life. |
30kA |
Imax 8/20us (Line-Neutral). Maximum surge level. |
50kA |
Residual voltage (Vpl) (Line-Neutral). (Let through voltage) |
<1100v (3kA, 8/20us, ( IEC61643-11) |
Safety disconnect |
Series thermal fusing on MOVs |
External disconnector requirement |
Max 125A HRC fuse |
Terminations |
Power 16mm |
|
Communications |
Alarms/indicators |
5 LED display, dry contact alarm relay output 250VAC/32VDC, 5A, 5kV isolation |
|
|
Environmental & Standards |
Enclosure rating |
IP20 |
Design standards |
IEC61643-11, ANSI/IEEE C62.41 Cat A & B, AS1768-2007 Cat A & B, UL1449ed3 type 4 |
Environment |
-10 to 60C, 0 to 95%RH (non-condensing) |