Technical
specifications |
2200 |
Rating
(VA/W) |
2200VA/2200W |
Format |
RT2U (tower/rack 2U) |
|
|
Electrical
characteristics |
|
Technology |
On-line
double conversion with Power Factor Correction (PFC)
system |
Nominal
voltage |
230V |
Input
voltage range |
176-276V
without derating (up to 100-276V with derating) |
Input
frequency range |
40-70Hz,
50/60Hz autoselection, frequency converter mode |
Efficiency |
up
to 93.5% in online mode (up to 98% in Hi-efficiency
mode) |
|
|
Connections |
|
Input |
1
IEC C20 (16A) or terminal block on HotSwap MBP HW
(Hard-Wired) |
Outputs |
8
IEC C13 (10A) sockets + 2 IEC C19 (16A) sockets |
Outputs
on HotSwap models |
4 FR/Schuko sockets or 3 BS sockets or 6
IEC 10A sockets or terminal blocks (HW version) |
Switched
outlet group |
|
|
|
Batteries |
|
Typical
backup times* |
800W |
9PX
1000 |
9 |
9PX
1000 + 1 EBM/+4 EBM |
47/188 |
9PX
1500 |
13 |
9PX
1500 + 1 EBM/+4 EBM |
52/192 |
9PX
2200 |
15 |
9PX
2200 + 1 EBM/+4 EBM |
74/297 |
9PX
3000 |
22 |
9PX
3000 + 1 EBM/+4 EBM |
83/307 |
Battery
management |
ABM
& temperature compensated charging method (user selectable), automatic
battery test, deep discharge protection, automatic recognition of external
battery units |
Communication |
|
Communication
ports |
1
USB port + 1 serial RS232 port + 1 mini-terminal block for remote ON/OFF +
1 mini-terminal block for remote power off + 1 mini-terminal block for
output relay |
Communication
slot |
1
slot for Network-MS card (included in netpack versions), ModBus-MS or
Relay-MS cards |
|
|
Operating
conditions, standards and approvals |
|
Operating
temeprature |
0
to 40C |
Typical
noise level |
40dB
|
Safety |
IEC/EN
62040-1, UL 1778, CSA 22.2 |
EMC |
IEC/EN
62040 -2, FCC Class B, CISPR22 Class B |
Approvals
& markings |
CE
/CB report (TUV) / cULus / EAC /RCM / KC / Energy
Star |
|
|
Dimensions
H x W x D in mm/ Weight |
|
UPS |
86.5*440*605/25kg |
|
|
Customer
service and support |
|
Warranty |
3
years on electronics, 2 years on batteries |
|
*
Backup times are approximate and may vary with equipment, configuration,
battery age, temperature, etc. |
|
|
Parts
numbers* |
|
UPS
RT2U |
9PX2200IRT2U |