General |
|
Topology |
On-line
double conversion with Power Factor Correction (PFC)
system |
Configuration |
Rack/Tower |
Part
Number |
9PX3000IRT3U |
Rating
(VA/Watts) |
3000/3000 |
Dimensions
(H x W x D, mm) |
130
x 440 x 485 |
Weight
(kg) |
27.4 |
Warranty |
3
years electronics, 2 years battery |
|
|
Electrical
Input |
|
Connection |
(1)
IEC-320-C20 |
|
|
|
|
Input
Voltage Range |
176-276V
without derating (up to 100-276V with derating) |
Nominal
Voltage |
200/208/220/230/240V |
Frequency |
50/60
Hz autoselection |
Frequency
Range |
40-70
Hz |
|
|
Electrical
Output |
|
Nominal
Voltage |
200/208/220/230/240V |
Output
Receptacles |
(8)
IEC-320-C13 |
|
|
|
|
|
(2)
IEC-320-C19 |
|
|
|
|
Efficiency
(Normal Mode) |
Up
to 94% in online mode (Up to 98% in Hi-efficiency
mode) |
Output
Frequency |
50/60
Hz autoselect, frequency converter mode |
|
|
Battery |
|
Battery
Management |
ABM
& Temperature compensated charging method (user selectable), Automatic
battery test, deep discharge protection, automatic recognition of external
battery units |
Extended
Battery Capability |
EBM
(3U) |
|
|
Communications |
|
User
Interface |
Multilingual
graphical LCD display |
Communication
Ports |
1
USB port + 1 serial RS232 port + 1 mini-terminal block for remote ON/OFF +
1 mini-terminal block for Remote Power Off + 1 mini-terminal block for
Output relay |
Communication
Slot |
1
slot for Network-MS card, ModBus-MS or Relay-MS cards |
|
|
Environmental
& Standards |
|
Audible
Noise |
40dB |
Operating
Temperature |
0
to 40C |
Safety
markings |
IEC/EN
62040-1, UL 1778, CSA 22.2 |
EMC
Markings |
IEC/EN
62040 -2 , FCC Class B, CISPR22 Class B |
Approvals |
CE
/CB report (TUV) / cULus / EAC / RCM / KC / Energy
Star |