General |
|
Topology |
On-line double
conversion with PFC (Power Factor Correction) system |
Configuration |
Rack/Tower |
Part
Number |
9PX11KiPM |
Rating
(VA/Watts) |
11000/10000 |
Dimensions (H x W x D,
mm) |
260 (6U) x 440 x
685 |
Weight
(kg) |
86 |
Warranty |
3 years on electronics,
2 years on battery |
|
|
Electrical
Input |
|
Connection |
Hardwired - see manual
for terminal block layout |
|
|
Input Voltage
Range |
176-276V without
derating (up to 100276V with derating) |
Nominal
Voltage |
200/208/220/230/240/250V |
Frequency |
50/60 Hz
autoselection |
Frequency
Range |
40-70
Hz |
Short Circuit
Current |
150
A |
THDI |
<5% |
|
|
Electrical
Output |
|
Voltages |
200/208/220/230/240/250V
+/ 1% |
Voltage
THD |
<
2% |
Output
Receptacles |
Hardwired - see manual
for terminal block layout |
|
|
Overload
Capacity |
102110% : 120s,
110125%: 60s, 125150%: 10s, >150%: 900ms |
Efficiency (Normal
Mode) |
Up to 95% in Online
mode, 98% in Hi-Efficiency mode |
Output
Frequency |
50/60 Hz autoselect,
frequency converter as standard |
Load Crest
Factor |
3:01 |
|
|
Battery
|
|
Battery
Management |
ABM and Temperature
compensated charging method (user selectable), automatic battery test,
deep discharge protection, automatic recognition of external battery
units. |
Extended Battery
Capability |
EBM
(3U) |
|
|
Communications |
|
User
Interface |
Multilingual graphical
LCD display |
Communication
Ports |
1 USB port, 1 RS232
serial port (USB and RS232 ports cannot be used simultaneously), 4 dry
contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote
power Off, 1 DB15 for parallel operation. |
Communication
Slot |
1 slot for Network-MS
card, ModBus-MS or Relay-MS cards |
|
|
Environmental &
Standards |
|
Audible
Noise |
<50dB |
Operating
Temperature |
0 to 40 degree C
continuous |
Safety
markings |
IEC/EN 62040-1, UL
1778, CSA 22.2 |
EMC
Markings |
IEC/EN 62040 -2 , FCC
Class A, IEC/EN 62040-3 (Performance), C-Tick |
Approvals |
CE, CB report (TUV), UL
(Power Module) |