General |
|
Topology |
On-line
double conversion with PFC (Power Factor Correction)
system |
Configuration |
Rack/Tower |
Part
Number |
9PX6Ki |
Rating
(VA/Watts) |
6000/5400 |
Dimensions
(H x W x D, mm) |
130
(3U) x 440 x 685 |
Weight
(kg) |
48 |
Warranty |
3
years on electronics, 2 years on battery |
|
|
Electrical
Input |
|
Connection |
Hardwired
- see manual for terminal block layout |
|
|
Input
Voltage Range |
176-276V
without derating (up to 100–276V with derating) |
Nominal
Voltage |
200/208/220/230/240V |
Frequency |
50/60
Hz autoselection |
Frequency
Range |
40-70
Hz |
Short
Circuit Current |
90
A |
THDI |
<5% |
|
|
Electrical
Output |
|
Voltages |
200/208/220/230/240V
+/– 1% |
Voltage
THD |
<
2% |
Output
Receptacles |
Hardwired
- see manual for terminal block layout |
|
|
|
(8)
IEC-320-C13 |
|
|
|
(2)
IEC-320-C19 |
|
|
Overload
Capacity |
102–110%
: 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms |
Efficiency
(Normal Mode) |
Up
to 94% in Online mode, 98% in Hi-Efficiency mode |
Output
Frequency |
50/60
Hz autoselect, frequency converter as standard |
Load
Crest Factor |
3:01 |
|
|
Battery |
|
Battery
Management |
ABM®
and Temperature compensated charging method (user selectable), automatic
battery test, deep discharge protection, automatic recognition of external
battery units. |
Extended
Battery Capability |
EBM
(3U) |
|
|
Communications |
|
User
Interface |
Multilingual
graphical LCD display |
Communication
Ports |
1
USB port, 1 RS232 serial port (USB and RS232 ports cannot be used
simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote
On/Off and 1 for remote power Off, 1 DB15 for parallel
operation. |
Communication
Slot |
1
slot for Network-MS card, ModBus-MS or Relay-MS cards |
|
|
Environmental
& Standards |
|
Audible
Noise |
<45dB |
Operating
Temperature |
0
to 40°C continuous |
Safety
markings |
IEC/EN
62040-1, UL 1778, CSA 22.2 |
EMC
Markings |
IEC/EN
62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance),
C-Tick |
Approvals |
CE,
CB report (TUV), UL |