Function |
PE8108A |
PE8108B |
PE8108G |
Electrical |
Nominal Input Voltage |
100 – 120 VAC |
100 – 240 VAC |
100 – 240 VAC |
Maximum Input Current |
15A Max; 12A(UL de-rated) |
15A Max; 12A(UL de-rated) |
10A Max |
Input Frequency |
50-60 Hz |
50-60 Hz |
50-60 Hz |
Input Connection |
NEMA 5-15P |
NEMA 6-15P |
IEC 60320 C14 |
Input Power |
1800 VA(Max); 1440 VA(UL de-rated) |
3120 VA(Max); 2496 VA(UL de-rated) |
2300 VA(Max) |
Outlet Type |
Total: 8 x NEMA 5-15R |
Total: 8 x IEC320 C13 |
Total: 8 x IEC320 C13 |
Nominal Output Voltage |
100 – 120 VAC |
100 – 240 VAC |
100 – 240 VAC |
Maximum Output Current (Outlet) |
NEMA 5-15R: 15A(Max); 12A(UL de-rated) |
C13: 15A(Max); 12A(UL de-rated) |
C13: 10A(Max) |
Maximum Output Current (Bank) |
15A(Max); 12A(UL de-rated) |
15A(Max); 12A(UL de-rated) |
10A(Max) |
Maximum Output Current (Total) |
15A(Max); 12A(UL de-rated) |
15A(Max); 12A(UL de-rated) |
10A(Max) |
Breakers |
1 x 15A Non-Fuse Breaker |
1 x 15A Non-Fuse Breaker |
1 x 15A Non-Fuse Breaker |
Metering |
Outlet level Current, Voltage, VA , PF and KWh
Monitoring |
Outlet level Current, Voltage, VA , PF and KWh
Monitoring |
Outlet level Current, Voltage, VA , PF and KWh
Monitoring |
Outlet Switching |
Yes |
Yes |
Yes |
Environment Sensor Ports |
2 |
2 |
2 |
Metering Accuracy |
Voltage Range: 100VAC ~ 250VAC +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% |
Power Range: 100W ~ Maximum Capacity +/- 2% |
Power Range: 100W ~ Maximum Capacity +/- 2% |
Power Range: 100W ~ Maximum Capacity +/-
2% |
Current Range: 0.1A~1A +/- 0.1A, 1A~20A
+/-1% |
Current Range: 0.1A~1A +/- 0.1A, 1A~20A
+/-1% |
Current Range: 0.1A~1A +/- 0.1A, 1A~20A
+/-1% |
Physical Properties |
Dimensions (L x W x H) |
43.24 x 22.04 x 4.40 cm |
43.24 x 22.04 x 4.40 cm |
43.24 x 22.04 x 4.40 cm |
(17.02 x 8.68 x 1.73 in.) |
(17.02 x 8.68 x 1.73 in.) |
(17.02 x 8.68 x 1.73 in.) |
Weight |
2.75 kg ( 6.06 lb ) |
2.75 kg ( 6.06 lb ) |
2.75 kg ( 6.06 lb ) |
Power Cord Length |
3 m |
3 m |
3 m |
Environmental |
Temperature (Operating / Storage) |
0 – 50°C / -20 – 60°C |
0 – 50°C / -20 – 60°C |
0 – 50°C / -20 – 60°C |
Humidity (Operating & Storage) |
0 – 80% RH, Non-Condensing |
0 – 80% RH, Non-Condensing |
0 – 80% RH, Non-Condensing |
Compliance |
EMC Verification |
FCC, Others by Request |
FCC, Others by Request |
CE, Others by Request |
Safety Verification |
TUV-CB, cTUVus, Others by Request |
TUV-CB, cTUVus, Others by Request |
TUV-CB, CE-LVD, GOST, Others by Request |
Note |
For some of rack mount products, please note that the
standard physical dimensions of WxDxH are expressed using a LxWxH
format. |