GENERAL |
|
Phase |
Three
Phase Tower UPS |
UPS
Topology |
Online
Double Conversion |
Energy
Saving Technology |
Online
ECO Mode Efficiency > 98% |
Normal
Mode Efficiency ( % ) |
95% |
Battery
Mode Efficiency ( % ) |
95% |
Active
PFC Compatibility |
Yes |
Parallel
Expansion (Max. Units) |
4 |
INPUT |
|
Dual
Power Inputs |
Yes |
Generator
Compatibility |
Yes |
Input
Voltage ( Vac ) |
Line
to Line (L-L): 380 ~ 415 Vac |
|
Line
to Neutral (L-N): 220 ~ 240 Vac |
Input
Voltage Range ( Vac ) |
Line
to Neutral (L-N): 132 ~ 276 Vac |
|
Line
to Line (L-L): 228 ~ 478 Vac |
Adjustable
Voltage Range ( Vac ) |
Line
to Neutral (L-N): 220 ~ 250 Vac |
|
Line
to Line (L-L): 380 ~ 435 Vac |
Input
Frequency ( Hz ) |
50
± 3 |
|
60
± 3 |
Rated
Input Current ( A ) |
14 |
Input
Power Factor |
0.99 |
Input
Connector Type |
Hardwire
Terminal Block |
OUTPUT |
|
Capacity
(VA) |
10000 |
Capacity
(Watts) |
9000 |
On
Battery Waveform |
Pure
Sine Wave |
Output
Voltage Setting |
Configurable |
Output
Frequency Setting |
Configurable |
Output
Voltage ( Vac ) |
Line
to Line (L-L): 380 ~ 415 Vac |
|
Line
to Neutral (L-N): 220 ~ 240 Vac |
Output
Voltage Tolerance ( % ) |
1.5
% |
Power
Factor |
0.9 |
ECO
Mode Voltage Tolerance |
±
10 % |
Overload
Protection |
Internal
Current Limiting , Circuit Breaker , Fuse |
Overload
Protection (Line Mode) |
105~110%
Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min,
>150% Load Immediately |
Overload
Protection (Battery Mode) |
105~110%
Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min,
>150% Load Immediately |
Overload
Protection (Bypass Mode) |
125~130%
Load for 10 min, 130~150% Load for 1 min, 150~400% Load for 1 sec,
>400% Load Immediately |
Crest
Factor |
3:01 |
Harmonic
Distortion (Linear Load) |
THD1% |
Harmonic
Distortion (Non-linear Load) |
THD5.5% |
Internal
Bypass |
Automatic
Bypass , Manual Bypass |
Maintenance
Bypass |
Yes |
Outlet
Type |
Hardwire
Terminal Block x 1 |
Typical
Transfer Time ( ms ) |
0 |
BATTERY |
|
Runtime
at Half Load ( min ) |
25 |
Runtime
at Full Load ( min ) |
12 |
Typical
Recharge Power ( % ) |
20
% x Power |
Recharge
Power Setting |
Configurable |
Charger
Voltage Tolerance ( % ) |
1% |
Smart
Battery Management (SBM) |
Yes |
User-replaceable |
No |
Battery
Quantity (Each RBP) ( pcs ) |
40 |
Battery
Voltage (Each RBP) ( V ) |
240 |
Single
Battery Capacity ( AH ) |
12
V 9 AH |
External
Battery Quantity |
12V
x 40pcs |
SURGE
PROTECTION & FILTERING |
|
EMI/RFI
Filtration |
Yes |
MANAGEMENT
& COMMUNICATIONS |
|
LCD
Panel |
Yes |
LCD
Information Display |
Operation
Type , Power Status , Battery Status , Load Status , Fault & Warning ,
Other Information , Event & Log |
LCD
Setting & Control |
Mode
Setting , Input & Output , Battery Setting , Communication , Event
& Log , Security Setting , Language |
LED
Indicators |
Yes |
Serial
Port |
RS232
x 1 + RS485 x 1 + Dry Contact x1 |
Dry
Contact (with Relay) |
Yes |
Emergency
Power Off (EPO) Port |
Yes |
Audible
Alarms |
Battery
Mode , Low Battery , Overload , Overcharge , Overheat , UPS Fault ,
Replace Battery |
Power
Management Software |
PowerPanel®
Business |
SNMP/HTTP
Remote Monitoring |
Yes
- with optional RMCARD205 |
PHYSICAL |
|
Form
Factor |
Tower |
Enclosure
Construction |
Metal |
Color |
Black |
Ingress
Protection |
IP20 |
PHYSICAL
SIZE - UPS MODULE |
|
Dimensions
(WxHxD) (mm.) |
250
x 715 x 840 |
Weight
(kg.) |
164 |
SHIPPING
DIMENSIONS |
|
Dimensions
(WxHxD) (mm.) |
400
x 930 x 1000 |
Weight
(kg.) |
173 |
ENVIRONMENTAL |
|
Operating
Temperature (°C) |
0
~ 40 |
Operating
Relative Humidity (Non-condensing) ( % ) |
0
~ 95 |
Operating
Elevation ( feet/meters ) |
≤1000,
Load Derated 1% per 100m from 1000m and 2000m |
Storage
Temperature (°C) |
-40
~ 70 |
Storage
Relative Humidity (Non-condensing) ( % ) |
0
~ 95 |
Audible
Noise at 1.5M from Surface of Unit ( dBA ) |
58 |
CERTIFICATIONS |
|
Certifications |
CE
, IEC62040-1 , IEC62040-2 |
WARRANTY |
|
Product
Warranty Period (Year) |
2 |
Battery
Warranty Period (Year) |
2 |